<ins id="60n1a"><optgroup id="60n1a"><menuitem id="60n1a"></menuitem></optgroup></ins>
    <samp id="60n1a"><tfoot id="60n1a"></tfoot></samp>
    <fieldset id="60n1a"><table id="60n1a"><kbd id="60n1a"></kbd></table></fieldset>
  • 
    
    <samp id="60n1a"></samp>
    <samp id="60n1a"></samp>
  • <fieldset id="60n1a"><table id="60n1a"></table></fieldset>
    Loading...

    XGN66A-12
    Category:High voltage switchgear
    Release date:2019-02-26 15:02:25
     

    XGN66A-12 metal fixed switchgear

    Overview
    XGN66A-12 box type (indoor) AC metal-enclosed switchgear (hereinafter referred to as switchgear) meets the national standard GB3906 "3 ~ 35kV AC metal-enclosed switchgear" and the Ministry of Power DL404 "Indoor AC high-voltage switchgear ordering technical conditions" requirements It also meets the requirements of the international standard IEC298 "AC metal-enclosed switchgear and control equipment above 1kV and below 52kV", and has two "five-proof" blocking functions. The circuit breaker has high reliability and good performance, and the "five-proof" interlocking mechanism is reliable and simple.
    Main use and scope of application
    The switchgear is suitable for 3.6~12kV three-phase AC 50Hz single busbar segmentation indoor unit. It is used for receiving and distributing electric energy, and has the functions of controlling, protecting and monitoring the circuit. It can be applied to all types of power plants. Substations, industrial and mining enterprises, high-rise buildings and other places can also be combined with ring network cabinets for use in opening and closing.

    Technical data

    Table 1 / switch cabinet technical parameters

    project unit Data
    Rated voltage (ie maximum operating voltage)  kV  12
    Rated insulation level 1min power frequency withstand voltage kV 42
    Lightning impulse withstand voltage  kV 75
    Rated frequency Hz  50
    Main busbar rated current A  800 1250 2000 2500 3150
    Branch busbar rated current A  630 1000 1250 2000 2500 3150
    4s thermal stable current  kA  20 31.5 40
    Rated dynamic current  kA 50 80 100
    Protection level  IP2X
    Dimensions (width × depth × height)  mm 900×950(1000)×2300 950×950(1000)×2300 1100×1000×2300

     

    Table 2 / Isolation switch technical parameters

    project name unit  GN19-10C/630 GN19-10C/1000 GN19-10C/2000 GN30-10/2500(3150)
    GN30-10/630 GN30-10/1000 GN30-10/2000
    GN30-10D/630 GN30-10D/1000 GN30-10D/2000
    Rated voltage kV 10
    Maximum working voltage kV  12
    Rated current A 630 1000 2000 2500 3500
    4s rated thermal stable current  kA 20 31.5 31.5 40
    Rated dynamic current  kA 50 80 80 100
    Lightning impulse withstand voltage kV 75
    1min power frequency withstand voltage  kV 42

    product structure
    The switch cabinet is a metal closed box structure as shown in Figure 2. The cabinet frame is assembled by bending the steel plate. The cabinet is divided into a circuit breaker room, a main bus room, a cable room, and a secondary component room.
    The top of the switchgear is the busbar compartment, the front of the busbar compartment is the secondary component room, the middle of the cabinet is the circuit breaker compartment, and the isolation switch operation interlocking mechanism is arranged on the right side (or the left side), and the current transformer and illumination are installed on the rear side. The device, etc., the lower part of the cabinet is a cable room, and can be equipped with an arrester.


     

     

    客服中心
    工作時間

    周一至周日

    8:00 - 18:00

    點擊這里給我發(fā)消息 銷售客服


    請直接QQ聯(lián)系!
    展開客服
    免费人成激情视频在线观看冫,AV无码国产淫穴高清一区二区三区,国产三级在线观看完整版,永久在线无码免费网站
    <ins id="60n1a"><optgroup id="60n1a"><menuitem id="60n1a"></menuitem></optgroup></ins>
      <samp id="60n1a"><tfoot id="60n1a"></tfoot></samp>
      <fieldset id="60n1a"><table id="60n1a"><kbd id="60n1a"></kbd></table></fieldset>
    • 
      
      <samp id="60n1a"></samp>
      <samp id="60n1a"></samp>
    • <fieldset id="60n1a"><table id="60n1a"></table></fieldset>